OpenBCM V1.08-5-g2f4a (Linux)

Packet Radio Mailbox

IZ3LSV

[San Dona' di P. JN]

 Login: GUEST





  
G8MNY  > TECH     11.08.08 01:00l 121 Lines 5592 Bytes #999 (0) @ WW
BID : 64965_GB7CIP
Read: GUEST
Subj: Edgcume Peebles Megger & Low R
Path: IZ3LSV<IK2XDE<DB0RES<ON4HU<ON0BEL<GB7CIP
Sent: 080810/2219Z @:GB7CIP.#32.GBR.EU #:64965 [Caterham] $:64965_GB7CIP
From: G8MNY@GB7CIP.#32.GBR.EU
To  : TECH@WW

By G8MNY                                        (New Jan 08)
(8 Bit ASCII Graphics use code page 473 or 850)
This is an old tester the engineers used to use for testing wiring
(e.g. telephone).
 ___________ 
³ÚÄÄÄÄÄÄÄÄÄ¿³
³³ .ú'~'ú. ³³  250V DC test voltage.
³³ú\      ú³³  Range 20 kê - 25 Mê (0.5M « scale)
³³  \      ³³  Low Ohms 0.02ê - 50ê (1ê « scale)
³ÀÄÄÄÄÄÄÄÄÄÙ³  Often in a Leather case.
³  [~~~~~]  ³
Þ   ~~~~~   Ý  9V PP4 battery (or a good PP3!)
Þ           Ý  LIVE circuit detector.
 Ý         Þ
 Ý         Þ
 ³_________³

PRINCIPLES
The meter uses an inverter to provide the 250V megger supply. In the idle push
button position there is an un calibrated warning meter mode. The low ohms uses
a reverse current bridge circuit.                     _______
                                                     ³Current³  LOW OHMS
       MEGGER                WARNING VOLTAGE         ³source ÃÄÄÄÄÄÄÄÄÄÄ¿
                                                     ÀÄÄÄÂÄÄÄÙ          ³
        /~~~\ +   +250V                                  ³ +/~~~\    Battery
+ProbeÄ´MeterÃÄÄRÄÄ¿        +ProbeÄRÄÄ´>ÃÄÄ¿     +ProbeÄÄÅÄ´MeterÃÄ¿    ³
        \___/ ÚÄÄÄÄÁÄÄÄ¿                   ³             ³  \___/  ³    ³
              ³InterterÃBatt               ³             R         ³    ³
              ÀÄÄÄÄÂÄÄÄÙ            /~~~\  ³             ³         ³    ³
-ProbeÄÄÄÄÄÄÄÄÄÄÄÄÄÙ        -ProbeÄ´MeterÃÄÙ     -ProbeÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÙ
                                    \___/

METER CIRCUIT
The circuit is made quite complex due to the switching around the 3 modes.

           ÚÄÄ´<ÃÄÄÄÄ¿                ÚÄÄÄÄÄÄÂÄÄÄÄÂÄÄÄÄÄ¿
           ³         ³  OHMS          ³    100R  _³_    ³
           ÃÄÄÄ´>ÃÄÄÄ´  \/            ³    Cal2  \_/   _³_
           ³         ³   |ÚÄÄ+9V      ³      ³   _³_   /_\'
           ³  /~~~\  ³   |À>oÄÄÄ¿     ³      e\³ \_/    ³ 
           ÃÄ´MeterÃÄ´   |  oÄÄÄ)ÄÄÄÄÄÙ   PNP3 ÃÄÄÁÄ220Ä´
           ³  \___/  ³   |      ³             /³        ³
           ³         ÃÄÄÄÄÄ>oÄÄÄ)Ä16kÄ<+250V ³          ³
           ÃÄ47Ä100ÄÄ´   |  oÄÄÄ)ÄÄÄÄÄÄÄÄÄÄÄÄ´ CONSTANT ³
           ³    Cal1 ³   |      ³            ³  CURRENT ³
           ³         ³ ÚÄÄÄ>oÄÄÄ)ÄÄÄÄ¿       ³  SOURCE  ³
           ³         ³ ³    oÄ¿ ³    ³      22R         ³
+ProbeÄo-oÄ)ÄÄÄÄÄÄÄÄÄ)ÄÁÄ3k6ÄÄ)Ä)Ä¿  ³      Cal3       220
      fuse ³         ÀÄÄÄÄÄÄÄÄ´ ³ ³ 33K      ³          ³
           ³            MEG   ³ ³ ³ _³_      ÀÄÄÄÄÄÄÄÄÄÄ´
           ³            \/ÚÄÄÄ)ÄÙ ³ \_/                 ³
           ³             |À>o ³   ³  ³                  ³
           ³             |  oÄ)ÄÄÄ)ÄÄ)ÄÄÄ>INV 9V        ³
           ³             |    ³   ³  ³                  ³
           ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ>oÄ)ÄÄÄ)ÄÄ)ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ´
           ³             |  oÄ)ÄÄÄÙ  ³                  ³
           ³             |ÚÄÄÄ)ÄÄÄÄÄÄÙ    +9V           ³
           ³              À>oÄÙ           _³_           ³
           ³                o¿             Ü            ³
           ÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙ             ³            ³
-ProbeÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÁÄ0V

                   INVERTER     __________
                           NPN³/   ³  ³   ³
+250V<ÄÄÄÄÄÄÂÄÄÂÄÄÄ2M2ÄÄÄÄÄÄÄÄ´   3k9 ³   ³
           === ³              ³\e  ³  ³   ³
         3n3³  À´<ÃÄÄ¿   ÚÄÄÄÄÄÄ)ÄÄ´ 1k2  ³+
            ³         )||(______³  ³  ³  ===
            ³         )||ÚÄÄÄÄÄÄ)ÄÄ´  ³   ³
            ³         )||(___   ³  ³  ³   ³
            ³         )||ÚÄÄÄ)ÄÄ)ÄÄ)ÄÄ´   ³
            ³         )||(   ³  ³  ³  ³   ³
            ÃÄÄÄÂÄÄÄÄÙ ||(   ³  ³  ³  ³   ³
            ³  +³2u2 ÚÄÄÄ´   ³  ³  ³  ³   ³
           6k8 ===   ³    \³ ³  ³  ³  ³   ³
INV 9V>Ä2R2Ä´   ³    ³ PNP2ÃÄ´ 4k7 ³  ³   ³
            ÃÄÄÄÙ    ³   e/³_³_ ³  ³  ³   ³
            ³         \³ ³  \_/ ³  ³  ³   ³
            ³      PNP1ÃÄÁÄÄÄÁÄÄÙ  ³  ³   ³
            ³        e/³           ³  ³   ³
            ÀÄÄÂÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÙ  ³   ³
              ===47u                  ³   ³
   0V >ÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÙ

CIRCUIT OPERATION
With the rocker switch idle the meter is connected to the probes via 33k & a
diode, so it warns of AC or +ve voltages connected, as well as providing a
discharge path to any voltage stored on the cable under test from meggering.

Pressing the Mê button puts 9V into the inverter, the 2 darlington connected
PNPs with the transformer form the invertor oscillator. The secondary is
rectified to provide the output DC voltage, which also turns on the NPN to
provide a voltage control feedback. The NPN turning on, takes base drive
current from PNP1 completing the control loop.

The 250V feeds an 18k to the meter to the +probe, a 3k6 in is the -probe lead.
Calibration is provided with Cal1 preset across the meter to set Zero & mid
scale ohms.

Pressing the ê button puts 9V into the constant current source consisting of 2
voltage limiters on the supply a zener & then 2 diodes, feeding the PNP base
giving exactly 0.6V across its emitter resistor Cal2 & hence constant current
from the collector. Cal2 sets the current which gives the full meter indication
on no load. The mid scale calibration (@10R) is done with Cal3 preset that
takes half the supply current at mid scale.

N.B. Calibration must be done in Cal1 Cal2 Cal3 order!

MODIFICATION
I have modified mine to give 550V for mains wiring MEGER testing. To do that I
added a diode & cap to make voltage doubler on the secondary, & then changed
the 16k for a 121k to keep it all calibrated.


Why don't U send an interesting bul?

73 de John G8MNY @ GB7CIP


Read previous mail | Read next mail


 21.09.2024 19:34:04lGo back Go up