Subj: Essential Mains Changeover
Path: IZ3LSV<IW0QNL<JH4XSY<F1OYP<GB7CIP
Sent: 121212/0041Z @:GB7CIP.#32.GBR.EU #:3760 [Caterham Surrey GBR] $:3760_GB7C
From: G8MNY@GB7CIP.#32.GBR.EU
To : TECH@WW
By G8MNY (Updated Dec 12)
(8 Bit ASCII graphics use code page 437 or 850, Terminal Font)
I designed this simple unit to bypass 230V mains problems at a local community
radio station that needs essential mains for 24/7 computers. The building's
Mains Consumer Unit was recently updated to have two Earth leakage Residule
Current Devices, feeding two Main Contact Breakers banks, but also with a
separate "Alternate Mon RCD feed" provided just to the UPS system.
NORMAL Bypass UPS Bypass
RELAY RELAY
Normal ÚÄÄÄÄÄÄÄ¿ ÚÄÄÄÄÄÄ¿
RCD feed >ÄÄÅÄo ³ ÚÄÄÄÄÄÄÅÄo ³
³ \ ³ ³ ³ \ ³
Alternate >ÄÄÅÄo \ÄÄÄÅÄÄÄ´ ÚÄÄÄÄÅÄo \ÄÄÅÄÄÄ>Essential
Non RCD ÀÄÄÄÂÄÄÄÙ ³ ³ ÀÄÄÄÂÄÄÙ Power Feed
Bypass ÚÁÄÁ¿ Bypass
³UPS³
ÀÄÂÄÙ
36V
Battery
CIRCUIT
Alternate Normal
Non RCD RCD
EÄÄÄÄÄÄÄÄÄEÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄE
Mains Mains ³ Essential
Plug Plug ³ Sockets
N L N L NORMAL ³ UPS 250V~ N L
³ ³ ³ ³ ÚÄÄÄ¿ ³ ÚÄÄÄ¿ 470n ³ ³
³ ³ ÃÄÄÄÄ)ÄÄ´30KÃÄ¿ ³ Ú´30KÃÄ´ÃÄÄ¿ ³ ³
³ ³ ³ ³ ÀÄÄÄÙ ³ ³ ³ÀÄÄÄÙ 15K ³ ³
Ãneon´ Ãneon´ Use 15K ³ ³ Use ³ Ãneon´
³ ³ ³ ÃÄÄÄ\ÄÄÄÄÙ ³ ÀÄÂneonÂÄ\ÄÙ ³ ³
³ ³ ³ o ³ ³ ÃÄÄÄo ³ ³
³ ÀÄÄÄÄ)ÄÄÄÄo\ÄÄÄÄÄÄÂÄÄÄÄÄ)ÄÄÄÄÄ)ÄÄÄÄ)ÄÄÄo\ÄÄÄÄ)ÄÄÄÄÙ
³ ³ NORMAL ³ ³ ³ ³ UPS ³
³ ÀÄÄÄÄo ³ ³ ÃÄÄÄÄ)ÄÄÄo ³
ÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄo\ÄÄÄÂÄÄ)ÄÄÄÄÄ)ÄÄÄÄÄ)ÄÄÄÄ)ÄÄÄo\ÄÄÄÄÙ
³ ³ ÚÄÄÁÄÄ¿ ³ ³
N³in³L ³E E³ N³out ³L IEC
ÚÁÄÄÁÄÄÁÄÄÄÄÄÁÄÄÁÄÄÄÄÁ¿Connectors
³ 1kW 36V 100% UPS ³
ÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙ
For maxamium flexibility the source & load plugs & sockets are the Standard UK
13A fused type.
The four neons indicate power status, & the two switches enable safe manual
override of the relays for Normal Mains circuit & UPS servicing etc.
I found good quality 3x 15A changeover AC relays with 30Kê coils, but they
would stay operated down to 140V! So to each I added series 15k 1W resistor to
get a better operate to failure voltages of 205 to 190V.
However on flattening UPS the battery, I discovered the UPS can put out DC,
blowing kit fuses (SMPSUs PCs OK)! So I add a series 250V AC Cap to the UPS
bypass relay to ensure the UPS gets bypassed if it does a mains wobbly again!
WARNING
Bypassing RCDs is not to be taken lightly! The station need for 24/7 essential
power is considered very important. Normal building mains is all RCD protected,
only the specialised kit on IEC distribution panels has the bypass capability.
And it can be easily be configured back to RCD only, for safer live mains while
wiring work is going on etc. you just unplugging the non RCD supply.
Why don't U send an interesting bul?
73 De John, G8MNY @ GB7CIP