This is an old tester the engineers used to use for testing wiring
(e.g. telephone).
___________
³ÚÄÄÄÄÄÄÄÄÄ¿³
³³ .ú'~'ú. ³³ 250V DC test voltage.
³³ú\ ú³³ Range 20 kê - 25 Mê (0.5M « scale)
³³ \ ³³ Low Ohms 0.02ê - 50ê (1ê « scale)
³ÀÄÄÄÄÄÄÄÄÄÙ³ Often in a Leather case.
³ [~~~~~] ³
Þ ~~~~~ Ý 9V PP4 battery (or a good PP3!)
Þ Ý LIVE circuit detector.
Ý Þ
Ý Þ
³_________³
PRINCIPLES
The meter uses an inverter to provide the 250V megger supply. In the idle push
button position there is an un calibrated warning meter mode. The low ohms uses
a reverse current bridge circuit. _______
³Current³ LOW OHMS
MEGGER WARNING VOLTAGE ³source ÃÄÄÄÄÄÄÄÄÄÄ¿
ÀÄÄÄÂÄÄÄÙ ³
/~~~\ + +250V ³ +/~~~\ Battery
+ProbeÄ´MeterÃÄÄRÄÄ¿ +ProbeÄRÄÄ´>ÃÄÄ¿ +ProbeÄÄÅÄ´MeterÃÄ¿ ³
\___/ ÚÄÄÄÄÁÄÄÄ¿ ³ ³ \___/ ³ ³
³InterterÃBatt ³ R ³ ³
ÀÄÄÄÄÂÄÄÄÙ /~~~\ ³ ³ ³ ³
-ProbeÄÄÄÄÄÄÄÄÄÄÄÄÄÙ -ProbeÄ´MeterÃÄÙ -ProbeÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÙ
\___/
METER CIRCUIT
The circuit is made quite complex due to the switching around the 3 modes.
ÚÄÄ´<ÃÄÄÄÄ¿ ÚÄÄÄÄÄÄÂÄÄÄÄÂÄÄÄÄÄ¿
³ ³ OHMS ³ 100R _³_ ³
ÃÄÄÄ´>ÃÄÄÄ´ \/ ³ Cal2 \_/ _³_
³ ³ |ÚÄÄ+9V ³ ³ _³_ /_\'
³ /~~~\ ³ |À>oÄÄÄ¿ ³ e\³ \_/ ³
ÃÄ´MeterÃÄ´ | oÄÄÄ)ÄÄÄÄÄÙ PNP3 ÃÄÄÁÄ220Ä´
³ \___/ ³ | ³ /³ ³
³ ÃÄÄÄÄÄ>oÄÄÄ)Ä16kÄ<+250V ³ ³
ÃÄ47Ä100ÄÄ´ | oÄÄÄ)ÄÄÄÄÄÄÄÄÄÄÄÄ´ CONSTANT ³
³ Cal1 ³ | ³ ³ CURRENT ³
³ ³ ÚÄÄÄ>oÄÄÄ)ÄÄÄÄ¿ ³ SOURCE ³
³ ³ ³ oÄ¿ ³ ³ 22R ³
+ProbeÄo-oÄ)ÄÄÄÄÄÄÄÄÄ)ÄÁÄ3k6ÄÄ)Ä)Ä¿ ³ Cal3 220
fuse ³ ÀÄÄÄÄÄÄÄÄ´ ³ ³ 33K ³ ³
³ MEG ³ ³ ³ _³_ ÀÄÄÄÄÄÄÄÄÄÄ´
³ \/ÚÄÄÄ)ÄÙ ³ \_/ ³
³ |À>o ³ ³ ³ ³
³ | oÄ)ÄÄÄ)ÄÄ)ÄÄÄ>INV 9V ³
³ | ³ ³ ³ ³
ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ>oÄ)ÄÄÄ)ÄÄ)ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ´
³ | oÄ)ÄÄÄÙ ³ ³
³ |ÚÄÄÄ)ÄÄÄÄÄÄÙ +9V ³
³ À>oÄÙ _³_ ³
³ o¿ Ü ³
ÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙ ³ ³
-ProbeÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÁÄ0V
INVERTER __________
NPN³/ ³ ³ ³
+250V<ÄÄÄÄÄÄÂÄÄÂÄÄÄ2M2ÄÄÄÄÄÄÄÄ´ 3k9 ³ ³
=== ³ ³\e ³ ³ ³
3n3³ À´<ÃÄÄ¿ ÚÄÄÄÄÄÄ)ÄÄ´ 1k2 ³+
³ )||(______³ ³ ³ ===
³ )||ÚÄÄÄÄÄÄ)ÄÄ´ ³ ³
³ )||(___ ³ ³ ³ ³
³ )||ÚÄÄÄ)ÄÄ)ÄÄ)ÄÄ´ ³
³ )||( ³ ³ ³ ³ ³
ÃÄÄÄÂÄÄÄÄÙ ||( ³ ³ ³ ³ ³
³ +³2u2 ÚÄÄÄ´ ³ ³ ³ ³ ³
6k8 === ³ \³ ³ ³ ³ ³ ³
INV 9V>Ä2R2Ä´ ³ ³ PNP2ÃÄ´ 4k7 ³ ³ ³
ÃÄÄÄÙ ³ e/³_³_ ³ ³ ³ ³
³ \³ ³ \_/ ³ ³ ³ ³
³ PNP1ÃÄÁÄÄÄÁÄÄÙ ³ ³ ³
³ e/³ ³ ³ ³
ÀÄÄÂÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÙ ³ ³
===47u ³ ³
0V >ÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÙ
CIRCUIT OPERATION
With the rocker switch idle the meter is connected to the probes via 33k & a
diode, so it warns of AC or +ve voltages connected, as well as providing a
discharge path to any voltage stored on the cable under test from meggering.
Pressing the Mê button puts 9V into the inverter, the 2 darlington connected
PNPs with the transformer form the invertor oscillator. The secondary is
rectified to provide the output DC voltage, which also turns on the NPN to
provide a voltage control feedback. The NPN turning on, takes base drive
current from PNP1 completing the control loop.
The 250V feeds an 18k to the meter to the +probe, a 3k6 in is the -probe lead.
Calibration is provided with Cal1 preset across the meter to set Zero & mid
scale ohms.
Pressing the ê button puts 9V into the constant current source consisting of 2
voltage limiters on the supply a zener & then 2 diodes, feeding the PNP base
giving exactly 0.6V across its emitter resistor Cal2 & hence constant current
from the collector. Cal2 sets the current which gives the full meter indication
on no load. The mid scale calibration (@10R) is done with Cal3 preset that
takes half the supply current at mid scale.
N.B. Calibration must be done in Cal1 Cal2 Cal3 order!
MODIFICATION
I have modified mine to give 550V for mains wiring MEGER testing. To do that I
added a diode & cap to make voltage doubler on the secondary, & then changed
the 16k for a 121k to keep it all calibrated.
Why don't U send an interesting bul?
73 de John G8MNY @ GB7CIP