3 PHASE POWER
This is how AC power is normally generated & distributed, it is more efficient
than other AC systems, except for DC that is the most efficient, but difficult
& costly to transform the voltage at high power.

The wire colour scheme may differ between countries & also the voltage!

The phase angle between phases is 120ø, because of this the voltages are added
up vectorialy, so at first sight 2x 230V does not make 400V.

Line
BROWN ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ          STAR LOADS                DELTA LOADS
(red)    /³\ /³\     /³\              o
         400V |       |             Brown                     Brown
         \³/ 400V     |              Load                       o
BLACK ÄÄÄÄÄÄÄÄÄÄÄÄÄ   |               ³                       /60ø\
(yellow) /³\  |  /³\  |          120ø o 120ø              400V     400V
         400V |   |   |             /   \               Load        Load
         \³/ \³/  |   |         Grey 120ø Black         / 60ø      60ø \
GREY  ÄÄÄÄÄÄÄÄÄ   |   |      Load           Load      o______ 400V ______o
(blue)   /³\      |   |      o                 o     Grey      Load    Black
         230V   230V 230V     If loads balanced             No Neutral
         \³/     \³/ \³/      centre = neutral &
BLUE  ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ       loads all get 230V
(black)  (neutral)


NEW COLOUR HAZARDS !
New EU colours are Brown Black Grey for Lives & Blue Neutral
            replace red yellow blue for Lives & black Neutral. Green/Yel earth.

    N.B. the lethal change for both BLACK & BLUE colours!

Also note the colour layout of new 3 phase 4 core cable means, that a joint can
not be straight to an old cable & bigger joints casings will be needed to allow
for at least 2 cores to be bridged!

Single phase will change from Red live, Black Neutral to Brown & Blue
respectifully. But highly confusing in a 3 phase board with both old black
wire loads for Neutrals & Black Bus feed for live! Brown & Blue sleeves are to
be used over Red & Black wires!


3 PHASE TRANSFORMERS
Like any transformer the voltage can be changed, or isolated etc. The
difference being that 3 legs of the transformer carry the windings rather than
just the middle. ÚÄÄÄÄÄÄÄÄÄÄÄ¿   The winding connections can be either STAR or
                 ³ ÚÄÄ¿ ÚÄÄ¿ ³   DELTA or combinations of both.
                ÚÁÄÁ¿ÚÁÄÁ¿ÚÁÄÁ¿  When cross connected star-delta a rotation of
      Windings->³ 1 ³³ 2 ³³ 3 ³  90øin phase occurs. (eg 30ø from other phases)
                ÀÂÄÂÙÀÂÄÂÙÀÂÄÂÙ               . 
      Laminated  ³ ÀÄÄÙ ÀÄÄÙ ³      |   or   / \   becomes   _ /  or   /'³
         Core  ->ÀÄÄÄÄÄÄÄÄÄÄÄÙ     / \      '---'              \      '\,³

(due to magneto striction audio the hum given off from the steel is @ 300Hz)


3 PHASE RECTIFICATION
With rectification 3 diodes gives about 30% ripple at 150Hz (3x supply) the
ripple is not much as singe phase, as some of the 120ø voltages overlap.
      ___________________
    _³_   _³_   _³_  /|\
    /_\   /_\   /_\   |         100% ´    _.-._   _.-._   _.-._  Â Ripple
R ÄÄÄÙ     ³     ³   Raw         70%_³   /     \ /     \ /       Á
           ³     ³    DC             ³  ³       ³       ³
Y ÄÄÄÄÄÄÄÄÄÙ     ³    |              ³ ³       ³ ³     ³ ³
                 ³    |              ³³       ³   ³   ³   ³
BÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙ    |              ÅÄÄÄÄÄÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄ
                     \³/             0ø      120 180 240 310 360ø
NÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ


3 PHASE BRIDGE RECTIFIERS
Only 6 diodes produce a 3 phase bridge & that gives about 14% @ 300Hz (6x
supply) ripple peak to peak, as more of the 60ø voltages overlap.
      ________________
    _³_   _³_   _³_ /|\                                        
    /_\   /_\   /_\  |        100% ´    _.-._.-._.-._.-._.-._  Â Ripple
R ÄÄÄ´     ³     ³   |        86% /³   /   / \ / \ / \ / \ /   ^
     ³     ³     ³   |             ³  ³   ³   ³   ³   ³   ³
Y ÄÄÄ)ÄÄÄÄÄ´     ³  Raw            ³ ³   ³   ³ ³ ³ ³ ³ ³ ³ ³
     ³     ³     ³  DC             ³³   ³   ³   ³   ³   ³   ³
BÄÄÄÄ)ÄÄÄÄÄ)ÄÄÄÄÄ´   |             ÅÄÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄ
    _³_   _³_   _³_  |             0ø  60  120 180 240 310 360ø
    /_\   /_\   /_\ \|/
     ÀÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄ


12 PHASE RECTIFIERS
With push pull or 3 phase bridge system, & using both star & delta windings
there can effectively be 12 lives that are only 30ø apart. This can also be
achieved with push pull phase on each leg of the transforner.

  |        \   /      \ | /
  *    +     *    =     * 
/   \        |        / | \

Using 2x 3 phase bridges or 12 winding & diodes the resultant ripple is only
about 3.6% @ 600Hz, assuming all the voltages are equal! Very little filtering
is then needed for say a 100kW Tx HT supply.
            ________________________
          _³_ _³_ _³_ _³_ _³_ _³_ /|\
Floating  /_\ /_\ /_\ /_\ /_\ /_\  |
  .   RDÄÄÄ´   ³   ³   ³   ³   ³   |   100% ´    _.-.-.-.-.-.-.-.-. = Ripple
 / \  YDÄÄÄ)ÄÄÄ´   ³   ³   ³   ³   |   96% /³   / / /\/\/\/\/\/\/\
'---' BDÄÄÄ)ÄÄÄ)ÄÄÄ´   ³   ³   ³   |        ³  ³ ³ ³ ³ ³ ³ ³ ³ ³ ³
Windings   ³   ³   ³   ³   ³   ³  Raw       ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³
      RSÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ´   ³   ³   DC       ³³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³
  |   YSÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ´   ³   |        ÅÄÄÂÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄÄÄÂÄ
 / \  BSÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ)ÄÄÄ´   |       0ø 30 60 120 180 240 310ø
          _³_ _³_ _³_ _³_ _³_ _³_  |
          /_\ /_\ /_\ /_\ /_\ /_\ \|/
           ÀÄÄÄÁÄÄÄÁÄÄÄÁÄÄÄÁÄÄÄÁÄÄÄÄ